Foot Candle Calculator

Calculate the lighting requirements for any space using IES standards

1Space & Lighting Details

= 538 lux

Length

Width

Check your fixture specifications for lumen output

Advanced Settings

2Lighting Requirements

21

Fixtures Needed

@ 5,000 lumens each

Total Lumens Required

100,840 lm

Total Floor Area

1,200 ft²

Estimated Wattage

~1,008 W

Lux Equivalent

538 lux

Lumen Method Formula

Lumens = (FC × Area) ÷ (CU × LLF)

FC = Target foot-candles

Area = Room area in square feet

CU = Coefficient of Utilization (0.5-0.9)

LLF = Light Loss Factor (0.7-0.9)

IES Lighting Standards

Warehouse30 fc (323 lux)
Office50 fc (538 lux)
Retail Store75 fc (807 lux)
Classroom50 fc (538 lux)
Hospital100 fc (1,076 lux)
Workshop75 fc (807 lux)
Parking Garage10 fc (108 lux)

Understanding Foot-Candles in Lighting Design

Foot-candles measure the amount of light that reaches a surface, making them essential for proper lighting design. Different tasks and spaces require different light levels - a warehouse needs less light than a surgical suite. Using the correct foot-candle levels ensures safety, productivity, and energy efficiency.

How the Lumen Method Works

This calculator uses the lumen method, the standard approach for calculating indoor lighting. It considers your target illuminance, room size, fixture efficiency (CU), and expected light degradation over time (LLF) to determine how many lumens and fixtures you need.

Lighting Design Tips

  • •For task lighting (desks, workbenches), aim for 50-75 foot-candles; ambient lighting can be lower
  • •Higher ceilings require more lumens - adjust the CU factor downward for spaces over 12 feet
  • •LED fixtures maintain their output better than fluorescent, so you can use a higher LLF (0.9 vs 0.7)
  • •Consider using multiple smaller fixtures for more even light distribution rather than fewer large ones

How this calculator works

  1. Area = length × width (meters are converted to feet).
  2. Lumens needed = target foot-candles × area ÷ (CU × LLF). This is the IES lumen method.
  3. Fixtures = lumens needed ÷ lumens per fixture, rounded up.
  4. Watts are estimated at 100 lumens per watt, a typical LED figure.

Worked example: 30 × 20 ft office at 50 fc

Computed by this calculator's own code (method v1.0.0) when this page was built on 2026-11-20.

Inputs
Area30 × 20 ft = 600 sq ft
Target50 fc
Fixture output5,000 lm
CU0.6
LLF0.8
Results
Lumens needed62,500 lm
Fixtures13
Estimated LED watts625 W
Target in lux538.2 lx

CU (coefficient of utilization) is the share of lamp lumens that reaches the work plane; LLF (light loss factor) allows for dirt and lumen depreciation. Use the fixture maker's photometric data when you have it.

Planning targets preset in this tool

SpaceFoot-candlesLux
Parking10108
Warehouse30323
Office / classroom50538
Retail / workshop75807
Hospital task1001,076

These are starting points. Check the current IES recommended practice for your space and task.

Assumptions and limits

  • Average illuminance only. It says nothing about uniformity or glare; a point-by-point layout is needed for that.
  • CU depends on room shape and surface reflectances. 0.6 and 0.8 are generic defaults.

Sources

  • Illuminating Engineering Society (IES) Lighting Handbook: lumen method (average illuminance = lumens × CU × LLF ÷ area).
  • NIST Special Publication 811, Guide for the Use of the International System of Units (1 fc = 10.7639 lx).