Wire Gauge Calculator
Find the right wire size for your LED project based on current and distance
1Project Requirements
Total current draw of your load in amps
Distance from power supply to load
3% recommended for LED strips, 5% for general use
2Recommended Wire Size
10 AWG
Recommended Wire Gauge
2.1% voltage drop
Max Rated Current
30 A
Wire Diameter
2.588 mm
Wire Gauge Comparison
AWG Quick Reference
Why Wire Gauge Matters
Choosing the correct wire gauge is critical for safety and performance. Wire that's too thin for the current load will heat up, waste energy, and can be a fire hazard. For LED installations, undersized wire also causes voltage drop, leading to dimmer LEDs at the end of long runs.
How This Calculator Works
This calculator considers your current requirements, wire length, and acceptable voltage drop to recommend the smallest (most economical) wire gauge that meets your needs. It also ensures the wire's ampacity rating exceeds your load current for safe operation.
Wire Selection Tips
- •Always round up to a larger wire gauge (smaller AWG number) when in doubt - it's safer and allows for future expansion
- •Consider using stranded wire for flexibility in LED installations, especially where the cable needs to bend
- •For outdoor or high-temperature environments, derate wire capacity by 20% or more
- •Copper is preferred for LED projects due to its lower resistance, but aluminum can work for longer, high-current runs where weight matters
How this calculator works
- For each gauge from 24 AWG to 10 AWG, work out the voltage drop over the round-trip length.
- Keep the gauges whose drop stays within your limit and whose ampacity covers the current.
- Recommend the thinnest gauge that passes both checks.
Worked example: 5 A at 12 V over 25 ft, 3% limit
Computed by this calculator's own code (method v1.0.0) when this page was built on 2026-11-20.
| Current | 5 A |
|---|---|
| One-way length | 25 ft |
| Supply | 12 V |
| Max drop | 3% |
| Wire | copper |
| Recommended gauge | 10 AWG |
|---|---|
| Drop with that gauge | 0.250 V |
| Percent drop | 2.08% |
14 AWG would carry the current but drops 5.26%, above the 3% limit.
Copper wire reference used by this calculator
| Gauge | Ω per 1000 ft at 20 °C | ≈ Ω per 1000 ft at 75 °C | Ampacity used (A) |
|---|---|---|---|
| 24 AWG | 25.670 | 31.219 | 2.1 |
| 22 AWG | 16.140 | 19.629 | 3 |
| 20 AWG | 10.150 | 12.344 | 5 |
| 18 AWG | 6.385 | 7.765 | 7 |
| 16 AWG | 4.016 | 4.884 | 10 |
| 14 AWG | 2.525 | 3.071 | 15 |
| 12 AWG | 1.588 | 1.931 | 20 |
| 10 AWG | 0.999 | 1.215 | 30 |
75 °C column estimated with α = 0.00393/°C. Ampacity values are this tool's own assumptions and are not taken from the NEC or any other code.
Assumptions and limits
- Resistance is for solid copper at 20 °C. In a hot ceiling or conduit, size up if you are close to the limit.
- Aluminum is approximated as 1.6 × copper resistance and 0.8 × copper ampacity.
- For mains (120/230 V) branch circuits, your local electrical code sets the minimum wire size, not this tool.
Sources
- ASTM B258 (AWG diameters) with the resistivity of annealed copper (IACS); values are for solid copper at 20 °C.
- Copper temperature coefficient of resistance: 0.00393 per °C at 20 °C.